for 132kW (175HP) 400V 3 Ph motor to 250A at high overload (Heavy Duty) or 150kW (200HP) to 302A when Fan/Pump rated, operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted). Includes 6901 Keypad.
Simple set-up and ready to run in VxF from its default settings.
Requires external choke - part number CO389936U401 (not included - see linked products below)
Size G - 455mm Wide x 465mm Deep x 1384mm High plus space required at sides for bars and above for roof mounting fan.
Weight - 108kg
Overload - 150% x 60 seconds and 180% for 0.5seconds at high overload rating or 110% for 10 seconds for fan/pump rating.
Switching frequency - 2.5kHz at full output, reducing to 1.2kHz at maximum overload.
Speed Control Range - 0/250Hz at continuous rating, or 120Hz if used to maximum overload.
Braking - Supplied with unit
4 x Analogue Inputs, 8 Digital Inputs, 3 Analogue outputs, 3 Digital outputs (relay contacts).
Input Current - 236A at high overload or 297A when Fan/Pump rating set.
Input Voltage - 380/460V three phase +-10% at 50/60Hz.
Input fuse - 300A at high overload or 350A when Fan/Pump rating set - to suit input bridge at 304000A²s
Cubicle mounting.
Rated at 40C Ambient.
Ventilation fan requires a separate 230V supply fused at 2A.
Heat Loss at max output - 2912W at high overload and 3482W when Fan/Pump rating set.
Full part number is - 690-433250G2-B00P00-A400 (was - 690PG/1320/400/0011/UK/0/0/0/0/B0/230/0). - Exactly the same as SSD Drives and Eurotherm Drives - 690PG-1320-400-0011-UK-0-0-0-0-B0-230-0